Leak detector VL 330
Vacuum leak detection system to monitor double walled steel or plastic tanks.
Type with alarmpressure in mbar:
VL 330
Alarm underpressure:
> 330 mbar
Operating pressure:
< 450 mbar
Tanks:
- double walled cylindrical tanks e.g. DIN 6608; 6616, 6617, 6623, 6624
- single walled tanks with an approved lining
- upright standing tanks with suction line e.g. DIN 6618/2;
- other approved tanks
Liquids:
liquids with a flash-point above > 55°C
z.B. heating oil, Diesel, engine oil
Approvals:
Z - 65.22 - 389
Type with alarmpressure in mbar:
VL 330
Alarm underpressure:
> 330 mbar
Operating pressure:
< 450 mbar
Tanks:
- double walled cylindrical tanks e.g. DIN 6608; 6616, 6617, 6623, 6624
- single walled tanks with an approved lining
- upright standing tanks with suction line e.g. DIN 6618/2;
- other approved tanks
Liquids:
liquids with a flash-point above > 55°C
z.B. heating oil, Diesel, engine oil
Approvals:
Z - 65.22 - 389